CoolAutomation 2026 Driver Suite 1.1.2 Release Notes ## [1.1.2] - 2026-10-24 ### Fixed - With `Send_ON_With_Mode` enabled, one mode press turns an OFF Zone on and selects the mode. The Zone checks the result and retries once if needed. - OFF takes priority over commands still waiting for that Zone, so a queued ON cannot turn it back on. A command already sent to the device finishes first. - Normal Zone traffic no longer fills the trace window. Manager `Debug_FB` shows when Debug is on. ### Install - Replace all five module pairs together. Manager adds `Debug_FB` on a previously unused output row; existing pins stay in place. - Rebuild the integrated SIMPL program with these modules. The ZIP does not contain a new compiled demo program. Official article: https://support.coolautomation.com/hc/en-us/articles/38853975839133-Crestron-SIMPL-Windows-Driver-Suite Support: https://support.coolautomation.com/hc/en-us/requests/new