This article applies to the following CoolMaster products:
- CoolMaster *
- CoolMasterPro
- CoolMasterNet
- CloudBox
Toshiba VRF - Service Adapter connection |
|
Terminal integration steps
The Toshiba adapter is programmed to align the outdoor unit with the correct indoor units.
In order to do that, we will run a test in the toolbox terminal.
- Type:
ostat2. You should receive the response:
Y1.000 Undefined
OKLook up the outdoor unit model from this list:
link Y1.100 SMMS
link Y1.100 SMMSe
link Y1.100 SHRMe
link Y1.100 SMMS-Mini
link Y1.100 SMMSu3. Copy the correct outdoor line to the toolbox terminal. For example:
link Y1.000 SMMS-Mini4. You should receive the response:
OK5. Boot the device by unplugging and replugging the power cord/type in the toolbox terminal:
boot 2Now, you will receive a different response when you type the "ostats" command in the toolbox terminal
ostat
Y1.000 SMMS-Mini LineAddr:1 CapCtrl:100 OilRecC:0 OilRecH:0 CStart:0 HStart:0 Defrost:0 OilEqCt:0 SnowFnCt:0
DownCtrl:0 UpCtrl:0 OCapCtrl:0 Demand:100 StopKeep:0 OnStrtHH:7 OnStrtMM:10 TotalCon:2 InvCurRl:255
HiPrsRel:0 DschTRel:0 CoolStop:1 HeatStop:0 SV2Start:0 SV2HPRel:0 SV2LPRel:0 SV2OilPr:0 LoFanOp:0
HtSinkRel:1 TotCtStp:-2
Y1.001 HP:4 Comp(1):20.4 FanMode:29 4wayVlv:1 Pd[psi]:294.0 Ps[psi]:91.3 TD1:76.2 TE:-0.8 TL:30.3 TG:36.5 TS:2.1
TU:-40.0 TO:1.0 CheckCd1:OK CheckCd2:00 MCUver:1.60 I1:5.12 PMV1:67 SV2:0 SV3A:0 SV5:0 SV4:0
TH:16.5 TL3:-100.0 TS3:-100.0 TK1:-999.9 PMV4:0