CoolMaster - Supported VRF Manufacturers Configuration & Specification

This article applies to the following CoolMaster products

  • CoolMaster
  • CoolMasterPro 
  • CoolMasterNet
  • CloudBox

CoolMaster VRF Central Control and Central Communications - list of supported VRF manufacturer brands & configuration:

Daikin

 

Daikin Interface DIII-NET
Max Indoors per Line 64
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals (F1F2 IN) / (F1F2 OUT)
CoolMaster Lines L1, L2
Comments
  • The number of supported "group addresses"/actual groups per DIII-Net line is 64.
  • In some system configurations it may allow connecting up to 128 IDUs
Service Data Yes
Service IDU comments Unique AirNet addresses required
H/W Required  

 

Mitsubishi Electric

 

Mitsubishi Electric Interface M-NET
Max Indoors per Line 50
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals TB3 (M1,M2) / TB7 (M1,M2)
CoolMaster Lines L1, L2
Comments  
Service Data Yes
Service IDU comments  
H/W Required  

 

Mitsubishi Heavy

 

Mitsubishi Heavy Interface SuperLink / New SuperLink
Max Indoors per Line 128
Max Refrigerant systems per Line 32
Connection IDU/ODU
Terminals A,B
CoolMaster Lines L4, L5, L6, L7
Comments  
Service Data No
Service IDU comments  
H/W Required  

 

Panasonic

 

Panasonic Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 16
Connection IDU/ODU
Terminals (U1,U2)
CoolMaster Lines L1, L2
Comments  
Service Data Yes
Service IDU comments  
H/W Required  

Sanyo

 

Sanyo Interface SNET
Max Indoors per Line 64
Max Refrigerant systems per Line 16
Connection IDU/ODU
Terminals (U1,U2)
CoolMaster Lines L1, L2
Comments  
Service Data No
Service IDU comments  
H/W Required  

Toshiba

 

Toshiba Interface TCC Link
Max Indoors per Line 64
Max Refrigerant systems per Line 16
Connection IDU/ODU
Terminals (U1,U2) / (U3,U4)
CoolMaster Lines L1, L2
Comments
  • Service data requires a Toshiba Service Adapter (supplied by CoolAutomation)
Service Data Yes
Service IDU comments  
H/W Required  

Hitachi

 

Hitachi Interface H-Link
Max Indoors per Line 160
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals 1,2
CoolMaster Lines L1, L2
Comments

 

Service Data Yes
Service IDU comments  
H/W Required  

Haier

 

Haier Interface PQ (MRV4 and earlier), 
Max Indoors per Line 64
Max Refrigerant systems per Line 1
Connection IDU/ODU
Terminals (U1,U2)/(U3,U4)
CoolMaster Lines L1, L2
Comments
  • For service data, CN31/CN32 is required to be connected to L4, L5, L6, L7
Service Data Yes
Service IDU comments  
H/W Required  

Haier (with Modbus Adapter)

 

Haier Interface PQ, MRV5
Max Indoors per Line 64
Max Refrigerant systems per Line 10
Connection Modbus/ODU
Terminals AB(Modbus)/PQ
CoolMaster Lines L4, L5, L6, L7
Comments
  • For service data, CN47 is required to be connected to L4, L5, L6, L7
Service Data Yes
Service IDU comments  
H/W Required  

LG (Connected on IDU-ODU line)

 

LG Interface  
Max Indoors per Line 128
Max Refrigerant systems per Line  
Connection IDU/ODU
Terminals CentA, CentB
CoolMaster Lines L4, L5, L6, L7
Comments

 

Service Data Yes
Service IDU comments  
H/W Required  

LG (connected on IDU line)

 

LG Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals IND-A. IND-B
CoolMaster Lines L4, L5, L6, L7
Comments

 

Service Data Yes
Service IDU comments  
H/W Required  

AUX

 

AUX Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line  
Connection IDU/ODU
Terminals A,B
CoolMaster Lines L4, L5, L6, L7
Comments

 

Service Data No
Service IDU comments  
H/W Required  

Gree GMV4

 

Gree GMV4 Interface GMV
Max Indoors per Line 16
Max Refregirant systems per Line 1
Connection ODU
Terminals G1,G2
CoolMaster Lines L4, L5, L6, L7
Comments

See details for Gree GMV5 and GMV6

Service Data No
Service IDU comments  
H/W Required  

Gree GMV5 & GMV6

 

Gree GMV5 &

Gree GMV 

Interface GMV
Max Indoors per Line 64
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals G1.G2
CoolMaster Line L8 (USB-A)
Comments

See details for Gree GMV5

Supported by Service App Yes
Service IDU comments  
H/W Required USB Adapter (Supplied by CoolAutomation)

Fujitsu

 

Fujitsu Interface LON
Max Indoors per Line 128
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals Z1, Z2/X1,X2
CoolMaster Lines L8 (USB-A)
Comments

 

Supported by Service App Yes
Service IDU comments  
H/W Required USB Echelon U10/U60 (Sold by 3rd party)

Midea

 

Midea Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 16
Connection IDU/ODU
Terminals XYE
CoolMaster Lines L4, L5, L6, L7
Comments

 

Service Data Yes
Service IDU comments  
H/W Required  

Samsung

 

Samsung Interface NASA
Max Indoors per Line 128
Max Refrigerant systems per Line 10
Connection ODU
Terminals R1,R2
CoolMaster Lines L4, L5, L6, L7
Comments

 

Service Data Yes
Service IDU comments  
H/W Required  

Chigo

 

Chigo Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 16
Connection  
Terminals IDU/ODU
CoolMaster Lines L4, L5, L6, L7
Comments  
Service Data No
Service IDU comments  
H/W Required  

Blue Star

 

Blue Star Interface  
Max Indoors per Line 255
Max Refrigerant systems per Line 10
Connection ODU
Terminals A.B
CoolMaster Lines L1, L2
Comments

 

Service Data No
Service IDU comments  
H/W Required  

Tadiran VRF

 

Tadiran VRF Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 10
Connection IDU/ODU
Terminals G1,G2
CoolMaster Lines L8 (USB-A)
Comments  
Service Data Yes
Service IDU comments  
H/W Required  

Tica

 

Tica Interface  
Max Indoors per Line 64
Max Refrigerant systems per Line 10
   
Terminals A2, B2
CoolMaster Lines L4, L5, L6, L7
Comments  
Service Data No
Service IDU comments  
H/W Required  