Daikin - Reading thermostat temperature sensor instead of return air temperature sensor

This article applies to the following CoolMaster products:

  • CoolMaster 
  • CoolMasterPro 
  • CoolMasterNet
  • CloudBox

CoolMaster is able to read the room temperature from the thermostat sensor instead of the return air sensor. 

This function is controlled from the unit's local wired controller (like BRC1E72).

Here are the settings to be made in order to activate:

CoolMaster will read ambient temperature measured by thermostat - local wired controller (like BRC1E72) if following field settings had being done on thermostat:

Setting 10-2 = 03 - Only the thermostat thermistor will be utilized by indoor unit.
Setting 10-5 = 02 - Room temperature value reported to CoolMasterNet by Indoor is taken from thermostat.


 