This article applies to the following CoolMaster products
- CoolMaster
- CoolMasterPro
- CoolMasterNet
- CloudBox
CoolMasterNet supports various HVAC systems, that have to be connected to designated lines L1-L8. These lines support single or multi-brand HVAC, based on the limitations, specified below.
HVAC connectivity
Line # | Manufacturer | Interface | Terminals | Polarity | Max IDU (manufacturer limitation) | Max ODU (Manufacturers limitation) |
---|---|---|---|---|---|---|
L1, L2 | Daikin | DIII-NET | F1, F2 | None | 64 * | 10** |
Sanyo | S-NET | U1, U2 | None | 64 | 16 | |
Panasonic | U1, U2 | None | 64 | 16 | ||
Toshiba | TCC LINK | U1, U2 | None | 64 | 16 | |
Mitsubishi Electric | M-NET | M1, M2 | None | 50 | 10 | |
Hitachi | H Link | 1, 2 | None | 160 | 10 | |
Haier | P, Q | None | 64 | 16 | ||
L4,L5,L6,L7
|
LG | Inter A Inter B | + - | 128 | - | |
Gree / GMV4 | A, B | + - | 16 | 4 | ||
Mitsubishi Heavy | SuperLink | A, B | + - | 128 | 10 | |
Samsung | F1F2 / R1R2 | + - | 64 | 10 | ||
Midea | X, Y, E | + - GND | 64 | 16 | ||
Kentatsu | X, Y, E | + - GND | 64 | 16 | ||
Trane | X, Y, E | + - GND | 64 | 16 | ||
Chigo | X, Y, E | + - GND | 64 | 16 | ||
Bluestar | A,B | + - | 64 | 10 | ||
Tica | A2,B2 | + - GND | 64 | 10 | ||
L8 via USB Host Port | Fujitsu (external LON USB adapter required) | LON (ANSI/CEA- 709.1-B) | X1, X2 | None | 128 | 10 |
Gree GMV5 GMV6 | USB Network interface | G1, G2 | None | 64 | 16 |
* 64 Group addresses or 128 IDUs
** 10 Systems
HVAC line interoperability
L1 | L2 | L4 | L5 | L6 | L7 | L8 | |
L1** | VV | V | V | V | V | ||
L2** | V | V | V | V | V | ||
L4 | V | V | V | V | V | V | |
L5** | V | V | V | V | V | ||
L6* ** | V | V | V | V | V | ||
L7* | V | V | V | V | V | ||
L8 | V | V | V | V | V | V |
Limitations:
- Total number of supported indoors (for all HVAC Lines) can not exceed 255 units
- *When DIP switches P1 and P2 are "ON", lines L6 and L7 cannot be used as separated lines. In this case the polarity on the HVAC cable connected to L7 will be automatically detected.
- **Line L2 can not be connected simultaneously with line L6 and line L1 can not be connected simultaneously with line L5.