This article applies to the following CoolMaster products
- CoolMaster
- CoolMasterPro
- CoolMasterNet
- CloudBox
CoolMaster VRF brands & manufacturers specifics:
Daikin
| Daikin | Interface | DIII-NET |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 10 | |
| Connection | ODU/*IDU | |
| Terminals |
F1 F2 out central controller line (outdoor to outdoor) Or F1 F2 in indoor line |
|
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | Yes, unique AirNet per indoor and system | |
| H/W Required |
Mitsubishi Electric
| Mitsubishi Electric | Interface | M-NET |
| Max Indoors per Line | 50 | |
| Max Refrigerant systems per Line | 10 | |
| Connection | ODU/IDU | |
| Terminals | TB7 (M1,M2) / TB3 (M1,M2) | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
Mitsubishi Heavy
| Mitsubishi Heavy | Interface | SuperLink / New SuperLink |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 32 | |
| Connection | ODU/IDU | |
| Terminals | A,B | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
Panasonic
| Panasonic | Interface | |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 15 | |
| Connection | ODU/IDU | |
| Terminals | 1,2 | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
Sanyo
| Sanyo | Interface | SNET |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU/IDU | |
| Terminals | 1,2 | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | No | |
| H/W Required |
Toshiba
| Toshiba | Interface | TCC-Link and TU2C-Link |
| Max Indoors per Line | 64* | |
| Max Refrigerant systems per Line | 15 | |
| Connection | ODU/IDU | |
| Terminals | (U3,U4) / (U1,U2) | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | TCC-Link - Yes TU2C-Link - No |
|
| H/W Required |
Hitachi
| Hitachi | Interface | H-Link |
| Max Indoors per Line | 160 | |
| Max Refrigerant systems per Line | 30 | |
| Connection | ODU/IDU | |
| Terminals | 1,2 | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
Haier (MRV4 and earlier)
| Haier (MRV4 and earlier) | Interface | P,Q (MRV4 and earlier) |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 1 | |
| Connection | IDU | |
| Terminals | P,Q | |
| CoolMaster Lines | L1, L2 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
Haier (with Modbus Adapter)
| Haier (with Modbus Adapter) | Interface | Modbus |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | Modbus adapter | |
| Terminals | Modbus adapter - U1(1,2) | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
|
|
| Service Data | Yes (via 3rd party, not through the professional app) | |
| H/W Required |
Haier (MRV5)
| Haier (MRV5) | Interface | Modbus |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU | |
| Terminals | A,B | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
|
|
| Service Data | Yes (via 3rd party, not through the professional app) | |
| H/W Required |
LG (connected Outdoor line)
| LG | Interface | CentA, CentB |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU | |
| Terminals | CentA, CentB | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
LG (connected on Indoor line)
| LG | Interface | LGMV |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 1 | |
| Connection | IDU | |
| Terminals | IND-A, IND-B | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
|
|
| Service Data | Yes | |
| H/W Required |
AUX
| AUX | Interface | |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | ||
| Connection | IDU/ODU | |
| Terminals | A,B | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments | ||
| Service Data | No | |
| H/W Required |
Gree GMV5 & GMV6
|
Gree GMV5 & Gree GMV |
Interface | Canbus |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 14* | |
| Connection | ODU | |
| Terminals | G1,G2 | |
| CoolMaster Line | L8 (USB-A) | |
| Comments | *By default each internal USB adapter line supports up to 7 systems, there are 2 lines. To join the lines and increase total system number contact our support | |
| Supported by Service App | Yes | |
| H/W Required | USB Adapter (Supplied by CoolAutomation) |
Fujitsu
| Fujitsu | Interface | LON |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU/IDU | |
| Terminals | Z1, Z2/X1,X2 | |
| CoolMaster Lines | L8 (USB-A) | |
| Comments | ||
| Supported by Service App | Yes | |
| H/W Required | USB Echelon U10/U60 (Sold by 3rd party) |
Midea (outdoor connection)
| Midea (ODU) | Interface | |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU | |
| Terminals | X,Y,E | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments |
• Each system and Indoor must be set with unique address • Midea V5 supports only indoor service data • Midea V6,V8 supports Outdoor and Indoor data • Do not Mix different Midea series on the same line |
|
| Service Data | Yes | |
| H/W Required |
Midea (indoor connection)
| Midea (IDU) | Interface | Non-VRF |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | N/A | |
| Connection | IDU | |
| Terminals | X,Y,E | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments | • Each Indoor must be set with unique address |
|
| Service Data | Yes | |
| H/W Required |
Samsung
| Samsung | Interface | DVM |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU/IDU* | |
| Terminals | R1,R2 / F1,F2 | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments | *IDU connection is allowed if only one system exist | |
| Service Data | Yes | |
| H/W Required |
Chigo
| Chigo | Interface | |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU | |
| Terminals | X,Y,E | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments | ||
| Service Data | No | |
| H/W Required |
Blue Star
| Blue Star | Interface | |
| Max Indoors per Line | 128 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ODU | |
| Terminals | A,B | |
| CoolMaster Lines | L4,L5,L6,L7 | |
| Comments | ||
| Service Data | No | |
| H/W Required |
Tica
| Tica | Interface | |
| Max Indoors per Line | 64 | |
| Max Refrigerant systems per Line | 16 | |
| Connection | ||
| Terminals | A2, B2 | |
| CoolMaster Lines | L4, L5, L6, L7 | |
| Comments | ||
| Service Data | No | |
| H/W Required |
HVAC Lines interoperability
| L1 | L2 | L3 | L4 | L5 | L6 | L7 | |
| L1** | v | v | v | v | v | v | |
| L2** | v | v | v | v | v | v | |
| L4 | v | v | v | v | v | v | |
| L5** | v | v | v | v | v | ||
| L6* ** | v | v | v | v | v | v | |
| L7* | v | v | v | v | v | v | |
| L8 | v | v | v | v | v | v |
- The total number of supported indoors (for all HVAC lines) can't exceed 255 units
- * When DIP switches P1 & P2 are "ON", lines L6 & L7 can't be used as separated lines. In this case, polarity in the HVAC cable connected to L7 will be automatically detected
- ** Line 1 can't be connected simultaneously with Line 5 and Line 2 can't be connected simultaneously with Line 6
- For more info and visuals please see the installation manual