Daikin VRV 3,4,5 – CoolMaster Outdoor line connection

This article applies to the following CoolMaster products:

  • CoolMaster 
  • CoolMasterPro 
  • CoolMasterNet
  • CloudBox

Daikin VRV 3,4,5 –Outdoor line connection

Maximum systems per line: 10

Maximum indoor per line: 64

  • Supported device line number: L1, L2
  • No line polarity required
  • Cable type – Follow Daikin's installation instructions
  • Set line type in the CoolMaster device to:  DK
  • Set dip switch according to the drawing
  • Follow DK instruction on how to address the units
  • Each Indoor must be set with group address for control
  • Each system and Indoor must be set with Airnet address if service data is required

 

Was this article helpful?
0 out of 0 found this helpful