Panasonic VRF – CoolMaster Indoor/Outdoor line connection

This article applies to the following CoolMaster products:

  • CoolMaster *
  • CoolMasterPro
  • CoolMasterNet
  • CloudBox

Panasonic VRF – Indoor / Outdoor line connection

Maximum systems per line: 15

Maximum indoor per line: 64

  • Supported device line number: L1, L2
  • No line polarity required
  • Cable type – Follow Panasonic's installation instructions
  • Set line type in the CoolMaster device to:  PS
  • Set dip switch according to the drawing
  • Follow Panasonic's instruction on how to address the units
  • Each outdoor and indoor must be set with groupaddress for control

 