CoolMaster EDGE LEAP (Lutron LEAP) Integration Guide

This article applies to the CoolMaster EDGE

Overview

This guide explains how to integrate a CoolMaster EDGE with a Lutron HomeWorks system. The integration is bi-directional, so both sides must be set up: first add the CoolMaster EDGE to the HomeWorks system (Part 3), then add the HomeWorks system to the CoolMaster EDGE (Part 4). Parts 1 and 2 cover the HomeWorks processor and Palladiom thermostat setup in Lutron Designer that the integration relies on.

Cool EDGE Lutron Integration.png

Before You Begin

  • Access to Lutron Designer
  • A HomeWorks processor (HQP7-2) and a Palladiom thermostat
  • The MAC address of your CoolMaster EDGE. You can find it on the label on the box, on the back of the device, and on the EDGE LCD screen. If the device is connected to a CoolAutomation cloud account (iocControl or Professional), it is also listed under SITE MANAGEMENT in the cloud apps.
  • A Windows PC with SetupUtility installed
  • An Ethernet connection to the same network as HomeWorks
  • A USB C cable (USB A to USB C is preferred)

Steps

Part 1: Add a HomeWorks processor in Lutron Designer

  1. Log in to Lutron Designer.
  2. Create a new project or open an existing one.
  3. On the Design tab, open the Equipment dropdown and click Edit toolbox.
  4. Choose the Devices group, select HQP7-2, click Add device, then click Done. 
  5. Drag and drop HW 2-Link Processor to Equipment Locations.
  6. Open the Activate tab and click Start discovery.
  7. When the processor is found, select it in the processors list and click the Activate link in the right panel.

     

Part 2: Add a Palladiom thermostat

  1. On the Design tab (controls), choose the Temperature group and drag HWQS Palladiom Thermostat to Device locations.
  2. On the Design tab (link assignment), go to Link 2 QS and check the newly created Thermostat 1. 
  3. On the Activate tab (devices), select Thermostat in the right panel and click Start Activation. If needed, click Sync and save. Then follow the on-screen instructions: press and hold any button on the thermostat for 6 seconds, then click the Activate link in the right panel.
  4. Activate the thermostat on the Activate page and follow the on-screen instructions. 

Part 3: Add the CoolMaster EDGE to the Lutron HomeWorks system

This part makes the CoolMaster EDGE known to HomeWorks. Part 4 completes the integration in the other direction.

  1. On the Design tab (equipment), click + to create a new group. Find and select 3rd party HVAC, click Add device, then click Done. 
  2. Drag and drop 3rd party HVAC to Equipment Locations.
  3. In the Manufacturer dropdown, select CoolMaster EDGE. 
  4. Assign a Unit ID in the format <EDGE MAC-address>-<LX.XXX>. Example: 283B9604000B-L1.001

    • L stands for line. The digit after it is the line number on the CoolMaster EDGE used to communicate with the HVAC equipment (any number from 1 to 9).
    • The three digits after the dot are the unit ID (UID), as defined in the CoolMaster manuals.
    • In the example, 283B9604000B is the MAC address, L1 is line 1, and 001 is the UID.

     

  5. On the Design tab (link assignment), go to Area 001 → Processor Panel 001 → Enclosure Panel 001 → Ethernet, and check your 3rd party HVAC device to activate it. 
  6. Assign the Palladiom thermostat to the 3rd party HVAC device: on the Design tab (controls), select the thermostat's Remote Zone tab, click the assign link in the HVAC Zone Name column, and choose the HVAC zone name you want to assign. 
  7. To enable full thermostat functionality, enable and select the operating modes and fan speeds in the corresponding columns of the output table. 

    Due to a limitation of the Palladiom thermostat setup, the thermostat's internal temperature sensor cannot be used with a Generic configuration.

  8. Go to the Transfer tab and click Start transfer. Allow approximately 5 minutes for the sync to complete. 

Part 4: Add the Lutron HomeWorks system to the CoolMaster EDGE

This part pairs the CoolMaster EDGE with your HomeWorks controller so the two communicate in both directions. It must be done in addition to Part 3.

  1. Install SetupUtility on your Windows PC.
  2. Connect the CoolMaster EDGE to the same network as HomeWorks via Ethernet, and to your PC via a USB C cable (USB A to USB C is preferred). 
  3. Open SetupUtility and connect to the CoolMaster EDGE.
  4. Run lutron discover to find your controller.
  5. Run lutron pair <XC controller id>. 
Was this article helpful?
0 out of 0 found this helpful