This article applies to the following CoolMaster products:
- CoolMaster
- CoolMasterPro
- CoolMasterNet
- CloudBox
Working with a CoolMaster device in parallel to the VRF brand-made central controller is mostly transparent but in some cases needs some settings/special connection.
The following table specifies details about CoolMaster-central controller coexistence.
| Brand | Parallel connection to the Cool device | Comments | Example model |
| Daikin | ✔️ |
ITM, DCS | |
| Mitsubishi Electric | ✔️ |
AE200 | |
| Toshiba | ✔️ |
CM1280 | |
| Panasonic | ✔️ |
CZ-256 | |
| Hitachi | ✔️ |
CCL01 | |
| Fujitsu | ✔️ |
UTY-DCGY | |
| Samsung | ✔️ |
MCM | |
| LG | ✔️ |
The VRF line setting in the CoolMaster needs to be defined as slave | AC Smart |
| Midea | ✖️ |
|
CCM |
| Mitsubishi Heavy (MHI) | ✔️ |
Automatically compatible as second Master | SC-SL4-AE |
| Haier | ✖️ |
|