Section 1: Current Release
Version: 1.0.4
Release Date: September 3, 2026
Download: CoolAutomation_2026_Module_Suite_Demo_Program_v1_0_4_compiled (attached)
Always download the latest version from this article. Files shared in forum posts, email threads, or third-party archives may be outdated.
Section 2: Overview
The CoolAutomation 2026 Crestron SIMPL+ Driver Suite provides direct PRM ASCII control of CoolAutomation HVAC gateways from Crestron SIMPL programs.
Supported devices:
- CoolMaster / CoolMaster Pro
- CoolMasterNet
- CooLinkHub
- CooLinkBridge
- CoolMaster Edge
-
CoolPlug
Section 3: Included Files
The production ZIP includes:
- Compiled SIMPL Windows demo program
- PDF help file
- Quick-start notes
- Release notes
Section 4: Basic Wiring
Use one CoolAutomation 2026 Manager module per CoolAutomation gateway.
For TCP/IP
Use a standard Crestron TCP/IP Client connected to port 10102.
For RS-232
Set Manager Transport_Mode to RS-232 and wire serial TX/RX directly to Manager TX$ / RX$.
Section 5: CoolMaster Edge Setup
CoolMaster Edge requires the ASCII server to be enabled before TCP port 10102 will accept connections.
Run this command once from a terminal or service tool:
set aserver enable 1
This cannot be performed automatically by the Crestron driver because the Manager module cannot connect until the ASCII server is already enabled.
Section 6: Child Modules
Use child modules as needed:
- Add one
CoolAutomation 2026 Zoneper HVAC indoor unit UID. - Add one
CoolAutomation 2026 Sensorper GS-SMT-IO point UID. - Add one
CoolAutomation 2026 HOA Zoneper GS-SMT-HOA heating zone UID. - Use
CoolAutomation 2026 CoolPlug Helperonly for CoolPlug commissioning tasks.
Section 7: Release Notes
1.0.4 - September 3, 2026
Production patch release. No pin/interface changes.
Fixed:
- Zone manager-bus parser now bounds
Mid()string lengths when parsingSTATE,NAME, andZONEERRmessages. - Prevents Zone string-range faults from malformed or shorter-than-expected Manager bus messages.
1.0.3 - August 27, 2026
- Enabled Zone louver/swing controls.
- Enabled Zone filter reset.
- Kept Manager console
Traceoutput gated behindDebug.
1.0.2 - August 27, 2026
- Gated Manager console
Traceoutput behindDebug.
1.0.1 - August 27, 2026
- Suppressed routine automatic empty-line
No UIDpoll noise. - Corrected Zone and HOA Zone UID documentation.
1.0.0 - August 23, 2026
- First official public production release.
Section 8: Support
For product and driver support, open a CoolAutomation support request:
https://support.coolautomation.com/hc/en-us/requests/new