Daikin Non VRV – CoolMaster EDGE Indoor connection
Yoram
Last update:
This article applies to the CoolMaster EDGE
Daikin non VRV – Indoor connection
Maximum indoor per line: 64
Supported device line number: L2
No line polarity required
Cable type – Follow Daikin installation instructions
Set line type in the EDGE device to: DK
In Case the line is not mixed with VRV units , set the Edge line DC power on, Caution – Apply power from the coolmaster Edge only if the line is free of power
Follow Daikin instructions on how to set up adapters address
EachIndoor adapter must be set with unique address for control