Daikin Non VRV – CoolMaster EDGE Indoor connection

This article applies to the CoolMaster EDGE

Daikin non VRV – Indoor connection

Maximum indoor per line: 64

  • Supported device line number: L2
  • No line polarity required
  • Cable type – Follow Daikin installation instructions
  • Set line type in the EDGE device to:  DK
  • In Case the line is not mixed with VRV units , set the Edge line DC power on, 
    Caution – Apply power from the coolmaster Edge only if the line is free of power
  • Follow Daikin instructions on how to set up adapters address
  • EachIndoor adapter must be set with unique address for control

 