BACnet Change of Value (COV)
Edge devices can now report BACnet updates as soon as a value changes, instead of polling. This gives faster updates with significantly less network traffic.
This also includes showing COV Increment value which indicates the resolution that will trigger a change. For example, an increment of 0.5° in a RoomTemp object, means changes of less than 0.5° will not be seen.
*Requires Edge FW version 1.13.0
Procedures for BACnet units
You can now include mapped BACnet units in Procedures, both to set Actions and to read values for setting Conditions. This is only available for BACnet devices that are mapped to universal units. The Universal units and their specific points (ON/OFF, setpoint, room temp, etc.) can then be used in conditions and Actions.
It allows you to automate a sequence of actions and checks on mapped BACnet devices (e.g. fan coils, rooftops etc) after mapping them to universal HVAC units.
Note: not any mapped BACNet point is supported. Only the point sthat are part of the HVAC universal unit point list.
CoolAutomation Modbus Library
A new shared library of ready-made Modbus devices and functional units, maintained by CoolAutomation. Find a device, download it straight to your site and edit it there, so you don’t have to build it from scratch.
Custom parameters in System Diagnostics
You can now add and see your custom defined indoor and outdoor parameters in System Diagnostics. These are the same parameters that are seen on the unit diagnostics and now it can also be tracked when in the system diagnostics screen.
The context of the parameter list is still, as before, at the site level.
Universal Units mapped on EDGE device
You can now use the “universal” command on the EDGE terminal to get a list of BACnet and Modbus units that are mapped to universal (HVAC unit, or power meter) and their names, address and state.
This allows easy tracking of which units can be mapped with VA addresses for server connectivity.
States legend: Missing - BACnet or Modbus unit has been deleted, Disengaged - ‘universal unchecked for this unit’, Disconnected - Unit does not respond, Connected - Unit is connected